Honeywell Experion LX through 2022-05-06 has Missing Authentication for a Critical Function. According to FSCT-2022-0055, there is a Honeywell Experion LX Control Data Access (CDA) EpicMo protocol with unauthenticated functionality issue. The affected components are characterized as: Honeywell Control Data Access (CDA) EpicMo (55565/TCP). The potential impact is: Firmware manipulation, Denial of service. The Honeywell Experion LX Distributed Control System (DCS) utilizes the Control Data Access (CDA) EpicMo protocol (55565/TCP) for device diagnostics and maintenance purposes. This protocol does not have any authentication features, allowing any attacker capable of communicating with the ports in question to invoke (a subset of) desired functionality. There is no authentication functionality on the protocol in question. An attacker capable of invoking the protocols' functionalities could issue firmware download commands potentially allowing for firmware manipulation and reboot devices causing denial of service.
Conclusion & alert: CVE-2022-30317 is rated Moderate Risk (53.9/100): CVSS Critical severity, with low exploitation likelihood (EPSS 0.72%). Mandatory action: Review affected assets and schedule remediation.
Risk is dynamic; we continuously reassess and refresh what is shown on this page as upstream context changes.
EPSS lead: Daily EPSS estimates relative likelihood of exploitation; percentile ranks this CVE among scored vulnerabilities (higher = more severe relative rank).
| # | Date | Old EPSS score | New EPSS score | Delta (New - Old) |
|---|---|---|---|---|
| 1 | 2026-06-15 | 0.32% | 0.72% | +0.40% |
| 2 | 2025-09-11 | 0.24% | 0.32% | +0.08% |
| 3 | 2025-09-02 | — | 0.24% | — |
Full EPSS history (9 records total)
CVSS metrics for this CVE.
| Base score | Version | Severity | Vector | Exploitability | Impact | Score source |
|---|---|---|---|---|---|---|
| 9.1 | 3.1 | CRITICAL |
|
3.9 | 5.2 | [email protected] |
| Vendor | Product | Version | Raw CPE |
|---|---|---|---|
| honeywell | experion_lx_firmware | < r520.1 | cpe:2.3:o:honeywell:experion_lx_firmware:*:*:*:*:*:*:*:* |
| URL | Tags |
|---|---|
| https://www.cisa.gov/uscert/ics/advisories/icsa-22-242-07 | Mitigation Third Party Advisory US Government Resource |
| https://www.forescout.com/blog/ | Not Applicable |