The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration.
Conclusion & alert: CVE-2026-3611 is rated Moderate Risk (52.7/100): CVSS Critical severity, with low exploitation likelihood (EPSS 0.16%). Mandatory action: Review affected assets and schedule remediation.
Risk is dynamic; we continuously reassess and refresh what is shown on this page as upstream context changes.
EPSS lead: Daily EPSS estimates relative likelihood of exploitation; percentile ranks this CVE among scored vulnerabilities (higher = more severe relative rank).
| # | Date | Old EPSS score | New EPSS score | Delta (New - Old) |
|---|---|---|---|---|
| 1 | 2026-03-18 | 0.13% | 0.16% | +0.03% |
| 2 | 2026-03-13 | — | 0.13% | — |
Full EPSS history (2 records total)
CVSS metrics for this CVE.
| Base score | Version | Severity | Vector | Exploitability | Impact | Score source |
|---|---|---|---|---|---|---|
| 10.0 | 4.0 | CRITICAL |
|
— | — | [email protected] |
| 10.0 | 3.1 | CRITICAL |
|
3.9 | 6.0 | [email protected] |
| Vendor | Product | Version | Raw CPE |
|---|---|---|---|
| No affected products in dataset. | |||