This page lists publicly disclosed CVE vulnerabilities affecting emerson controlwave_micro_firmware (linked via NVD CPE). Each row includes severity scores, summaries, and publication dates to help identify and analyze security issues.
| CVE | Summary | Source | Max CVSS | EPSS % | Published | Updated |
|---|---|---|---|---|---|---|
| CVE-2022-30262 | The Emerson ControlWave 'Next Generation' RTUs through 2022-05-02 mishandle firmware integrity. They utilize the BSAP-IP protocol to transmit firmware updates. Firmware updates are supplied as CAB archive files containing a binary firmware image. In all cases, firmware images were found to have no authentication (in the form of firmware signing) and only relied on insecure checksums for regular integrity checks. | [email protected] | 7.8 | 0.04% | 2022-08-17 | 2024-11-21 |
| CVE-2018-5452 | A Stack-based Buffer Overflow issue was discovered in Emerson Process Management ControlWave Micro Process Automation Controller: ControlWave Micro [ProConOS v.4.01.280] firmware: CWM v.05.78.00 and prior. A stack-based buffer overflow vulnerability caused by sending crafted packets on Port 20547 could force the PLC to change its state into halt mode. | [email protected] | 7.5 | 1.69% | 2018-03-07 | 2024-11-21 |