汇总 inea 相关全部产品的 CVE 与安全漏洞情报,包括 CVSS、EPSS、公开时间与漏洞情报数据。
历史漏洞主要涉及 跨站脚本与命令注入 等问题,部分漏洞可能导致 会话劫持,并影响 软件部署与生产负载 相关场景。
相关漏洞数据主要来源于公开漏洞披露与安全公告,可用于评估历史漏洞暴露面与修复优先级。
| CVE | 摘要 | 来源 | 最高 CVSS | EPSS % | 公开时间 | 更新时间 |
|---|---|---|---|---|---|---|
| CVE-2023-35762 | Versions of INEA ME RTU firmware 3.36b and prior are vulnerable to operating system (OS) command injection, which could allow remote code execution. | [email protected] | 9.9 | 1.70% | 2023-11-20 | 2026-06-17 |
| CVE-2023-29155 | Versions of INEA ME RTU firmware 3.36b and prior do not require authentication to the "root" account on the host system of the device. This could allow an attacker to obtain admin-level access to the host system. | [email protected] | 9.8 | 0.86% | 2023-11-20 | 2026-06-17 |
| CVE-2023-2131 | Versions of INEA ME RTU firmware prior to 3.36 are vulnerable to OS command injection, which could allow an attacker to remotely execute arbitrary code. | [email protected] | 10.0 | 1.73% | 2023-04-20 | 2026-06-17 |
| CVE-2019-14931 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote OS Command Injection vulnerability allows an attacker to execute arbitrary commands on the RTU due to the passing of unsafe user supplied data to the RTU's system shell. Functionality in mobile.php provides users with the ability to ping sites or IP addresses via Mobile Connection Test. When the Mobile Connection Test is submitted, action.php is ca | [email protected] | 9.8 | 57.66% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14930 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Undocumented hard-coded user passwords for root, ineaadmin, mitsadmin, and maint could allow an attacker to gain unauthorised access to the RTU. (Also, the accounts ineaadmin and mitsadmin are able to escalate privileges to root without supplying a password due to insecure entries in /etc/sudoers on the RTU.) | [email protected] | 9.8 | 2.34% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14929 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Stored cleartext passwords could allow an unauthenticated attacker to obtain configured username and password combinations on the RTU due to the weak credentials management on the RTU. An unauthenticated user can obtain the exposed password credentials to gain access to the following services: DDNS service, Mobile Network Provider, and OpenVPN service. | [email protected] | 9.8 | 1.94% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14928 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. A number of stored cross-site script (XSS) vulnerabilities allow an attacker to inject malicious code directly into the application. An example input variable vulnerable to stored XSS is SerialInitialModemString in the index.php page. | [email protected] | 5.4 | 44.15% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14927 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. An unauthenticated remote configuration download vulnerability allows an attacker to download the smartRTU's configuration file (which contains data such as usernames, passwords, and other sensitive RTU data). | [email protected] | 7.5 | 41.85% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14926 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. Hard-coded SSH keys allow an attacker to gain unauthorised access or disclose encrypted data on the RTU due to the keys not being regenerated on initial installation or with firmware updates. In other words, these devices use private-key values in /etc/ssh/ssh_host_rsa_key, /etc/ssh/ssh_host_ecdsa_key, and /etc/ssh/ssh_host_dsa_key files that are publicly available from the | [email protected] | 9.8 | 2.08% | 2019-10-28 | 2026-06-16 |
| CVE-2019-14925 | An issue was discovered on Mitsubishi Electric Europe B.V. ME-RTU devices through 2.02 and INEA ME-RTU devices through 3.0. A world-readable /usr/smartrtu/init/settings.xml configuration file on the file system allows an attacker to read sensitive configuration settings such as usernames, passwords, and other sensitive RTU data due to insecure permission assignment. | [email protected] | 6.5 | 1.26% | 2019-10-28 | 2026-06-16 |