Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Conclusion & alert: CVE-2022-33174 is rated High Exploit Risk (83.8/100): CVSS Critical severity, with high exploitation likelihood (EPSS 72.03%, 99th percentile). Core evidence: 1 public exploit reference(s) are indexed (Exploit-DB). Mandatory action: Public exploits are available—assess exposure, apply mitigations, and prioritize patching.
Risk is dynamic; we continuously reassess and refresh what is shown on this page as upstream context changes.
| EDB-ID | Source | Kind | Published | Link |
|---|---|---|---|---|
| — | nvd_ref | exploit_tag | Exploit-DB ↗ |
EPSS lead: Daily EPSS estimates relative likelihood of exploitation; percentile ranks this CVE among scored vulnerabilities (higher = more severe relative rank).
| # | Date | Old EPSS score | New EPSS score | Delta (New - Old) |
|---|---|---|---|---|
| 1 | 2026-03-05 | 81.72% | 72.03% | -9.69% |
| 2 | 2025-11-21 | 63.87% | 81.72% | +17.84% |
| 3 | 2025-11-18 | — | 63.87% | — |
Full EPSS history (30 records total)
CVSS metrics for this CVE.
| Base score | Version | Severity | Vector | Exploitability | Impact | Score source |
|---|---|---|---|---|---|---|
| 9.8 | 3.1 | CRITICAL |
|
3.9 | 5.9 | [email protected] |
| 7.5 | 3.1 | HIGH |
|
3.9 | 3.6 | [email protected] |
| 5.0 | 2.0 | MEDIUM |
|
10.0 | 2.9 | [email protected] |
| Vendor | Product | Version | Raw CPE |
|---|---|---|---|
| powertekpdus | basic_pdu_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:basic_pdu_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | pm_pdu_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:pm_pdu_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | piml_pdu_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:piml_pdu_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | smart_pim_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:smart_pim_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | smart_pos_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:smart_pos_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | smart_pom_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:smart_pom_firmware:*:*:*:*:*:*:*:* |
| powertekpdus | smart_poms_firmware | < 3.30.30 | cpe:2.3:o:powertekpdus:smart_poms_firmware:*:*:*:*:*:*:*:* |
| URL | Tags |
|---|---|
| https://gynvael.coldwind.pl/?lang=en&id=748 | Exploit Third Party Advisory |