CVE-2022-33175 Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device. [email protected] 9.8 1.66% 2022-06-13 2024-11-21
CVE-2022-33174 Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the user [email protected] 9.8 13.43% 2022-06-13 2024-11-21